1-1/4-inch ENT Conduit Fill

Wire capacity of trade size 1-1/4 (metric designator 35) Electrical Nonmetallic Tubing, for THHN, XHHW, THW and RHW conductors from 14 AWG to 1000 kcmil.

1-1/4-inch ENT holds 60 × #14, 43 × #12, 27 × #10 or 16 × #8 THHN conductors at 40% fill. Internal area: 1.453 in²; usable at 40%: 0.581 in².

Internal diameter
1.360 in · 34.5 mm
Total area
1.453 in² · 937 mm²
40% fill (3+ wires)
0.581 in²
31% / 53% (2 / 1 wire)
0.450 / 0.770 in²
Maximum conductors in 1-1/4-inch ENT
Wire sizeTHHNXHHWTHWRHWTHHN in a nipple (60%)THHN area (in²)
14 AWG60424220900.0097
12 AWG43323216650.0133
10 AWG27242413410.0211
8 AWG1613137240.0366
6 AWG111085170.0507
4 AWG7764100.0824
3 AWG665490.0973
2 AWG554370.1158
1 AWG333150.1562
1/0 AWG332140.1855
2/0 AWG221140.2223
3/0 AWG111130.2679
4/0 AWG111120.3237
250 kcmil111120.3970
300 kcmil111120.4608
350 kcmil11110.5242
400 kcmil11110.5863
500 kcmil1110.7073
600 kcmil10.8676
700 kcmil10.9887
750 kcmil11.0496
800 kcmil1.1085
900 kcmil1.2311
1000 kcmil1.3478

Mixed wire sizes? Calculate it

Loading calculator…

1-1/4-inch conduit: ENT vs other types

Trade size is nominal. The real inside diameter, and so the wire count, changes with the wall thickness of each raceway type.

1-1/4-inch trade size across conduit types
Conduit typeID (in)Area (in²)40% (in²)#12 THHN#10 THHN#6 THHN
EMT1.3801.4960.598452812
PVC Schedule 401.3601.4530.581432711
PVC Schedule 801.2551.2370.49537239
Rigid Metal Conduit1.3941.5260.610462912
IMC1.4481.6470.659493113
Flexible Metal Conduit1.2751.2770.511382410
Liquidtight Flexible Metal Conduit1.3951.5280.611462912
ENT1.3601.4530.581432711

Other ENT sizes

Frequently asked questions

How many #12 wires fit in 1-1/4-inch ENT?

43 conductors of 12 AWG THHN/THWN-2 at the 40% fill limit. With thicker THW or XHHW insulation the count is 32.

What is the inside diameter and area of 1-1/4-inch ENT?

The internal diameter is 1.360 in. (34.5 mm) and the total cross-sectional area is 1.453 in². The usable area is 0.581 in² at 40% fill, 0.450 in² for two wires and 0.770 in² for one.

What is the largest wire I can pull three of in 1-1/4-inch ENT?

1/0 AWG THHN: 3 conductors fit at 40% fill. That is three current-carrying conductors with no ground; add the ground’s area and check again with the calculator if you need one.

Can I really load it with that many conductors?

For space, yes. But 43 current-carrying conductors in one raceway means heavy ampacity derating — 10 to 20 conductors are adjusted to 50% of their table ampacity. Fill tells you what fits; derating tells you what it can carry.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.