1-1/4-inch IMC Conduit Fill

Wire capacity of trade size 1-1/4 (metric designator 35) Intermediate Metal Conduit, for THHN, XHHW, THW and RHW conductors from 14 AWG to 1000 kcmil.

1-1/4-inch IMC holds 68 × #14, 49 × #12, 31 × #10 or 18 × #8 THHN conductors at 40% fill. Internal area: 1.647 in²; usable at 40%: 0.659 in².

Internal diameter
1.448 in · 36.8 mm
Total area
1.647 in² · 1063 mm²
40% fill (3+ wires)
0.659 in²
31% / 53% (2 / 1 wire)
0.511 / 0.873 in²
Maximum conductors in 1-1/4-inch IMC
Wire sizeTHHNXHHWTHWRHWTHHN in a nipple (60%)THHN area (in²)
14 AWG684747221020.0097
12 AWG49363618740.0133
10 AWG31272715470.0211
8 AWG1815158270.0366
6 AWG131196190.0507
4 AWG8865120.0824
3 AWG6764100.0973
2 AWG555380.1158
1 AWG443160.1562
1/0 AWG333150.1855
2/0 AWG331140.2223
3/0 AWG111130.2679
4/0 AWG111130.3237
250 kcmil111120.3970
300 kcmil111120.4608
350 kcmil111120.5242
400 kcmil111110.5863
500 kcmil11110.7073
600 kcmil1110.8676
700 kcmil10.9887
750 kcmil11.0496
800 kcmil11.1085
900 kcmil11.2311
1000 kcmil1.3478

Mixed wire sizes? Calculate it

Loading calculator…

1-1/4-inch conduit: IMC vs other types

Trade size is nominal. The real inside diameter, and so the wire count, changes with the wall thickness of each raceway type.

1-1/4-inch trade size across conduit types
Conduit typeID (in)Area (in²)40% (in²)#12 THHN#10 THHN#6 THHN
EMT1.3801.4960.598452812
PVC Schedule 401.3601.4530.581432711
PVC Schedule 801.2551.2370.49537239
Rigid Metal Conduit1.3941.5260.610462912
IMC1.4481.6470.659493113
Flexible Metal Conduit1.2751.2770.511382410
Liquidtight Flexible Metal Conduit1.3951.5280.611462912
ENT1.3601.4530.581432711

Other IMC sizes

Frequently asked questions

How many #12 wires fit in 1-1/4-inch IMC?

49 conductors of 12 AWG THHN/THWN-2 at the 40% fill limit. With thicker THW or XHHW insulation the count is 36.

What is the inside diameter and area of 1-1/4-inch IMC?

The internal diameter is 1.448 in. (36.8 mm) and the total cross-sectional area is 1.647 in². The usable area is 0.659 in² at 40% fill, 0.511 in² for two wires and 0.873 in² for one.

What is the largest wire I can pull three of in 1-1/4-inch IMC?

2/0 AWG THHN: 3 conductors fit at 40% fill. That is three current-carrying conductors with no ground; add the ground’s area and check again with the calculator if you need one.

Can I really load it with that many conductors?

For space, yes. But 49 current-carrying conductors in one raceway means heavy ampacity derating — 10 to 20 conductors are adjusted to 50% of their table ampacity. Fill tells you what fits; derating tells you what it can carry.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.