1-1/4-inch PVC Schedule 80 Conduit Fill

Wire capacity of trade size 1-1/4 (metric designator 35) Rigid PVC Conduit, Schedule 80, for THHN, XHHW, THW and RHW conductors from 14 AWG to 1000 kcmil.

1-1/4-inch PVC Schedule 80 holds 51 × #14, 37 × #12, 23 × #10 or 13 × #8 THHN conductors at 40% fill. Internal area: 1.237 in²; usable at 40%: 0.495 in².

Internal diameter
1.255 in · 31.9 mm
Total area
1.237 in² · 798 mm²
40% fill (3+ wires)
0.495 in²
31% / 53% (2 / 1 wire)
0.383 / 0.656 in²
Maximum conductors in 1-1/4-inch PVC Schedule 80
Wire sizeTHHNXHHWTHWRHWTHHN in a nipple (60%)THHN area (in²)
14 AWG51353517760.0097
12 AWG37272714560.0133
10 AWG23202011350.0211
8 AWG1311116200.0366
6 AWG9874140.0507
4 AWG665390.0824
3 AWG554370.0973
2 AWG443360.1158
1 AWG332140.1562
1/0 AWG221140.1855
2/0 AWG111130.2223
3/0 AWG111120.2679
4/0 AWG111120.3237
250 kcmil111120.3970
300 kcmil11110.4608
350 kcmil11110.5242
400 kcmil1110.5863
500 kcmil10.7073
600 kcmil10.8676
700 kcmil0.9887
750 kcmil1.0496
800 kcmil1.1085
900 kcmil1.2311
1000 kcmil1.3478

Mixed wire sizes? Calculate it

Loading calculator…

1-1/4-inch conduit: PVC Schedule 80 vs other types

Trade size is nominal. The real inside diameter, and so the wire count, changes with the wall thickness of each raceway type.

1-1/4-inch trade size across conduit types
Conduit typeID (in)Area (in²)40% (in²)#12 THHN#10 THHN#6 THHN
EMT1.3801.4960.598452812
PVC Schedule 401.3601.4530.581432711
PVC Schedule 801.2551.2370.49537239
Rigid Metal Conduit1.3941.5260.610462912
IMC1.4481.6470.659493113
Flexible Metal Conduit1.2751.2770.511382410
Liquidtight Flexible Metal Conduit1.3951.5280.611462912
ENT1.3601.4530.581432711

Other PVC Schedule 80 sizes

Frequently asked questions

How many #12 wires fit in 1-1/4-inch PVC Schedule 80?

37 conductors of 12 AWG THHN/THWN-2 at the 40% fill limit. With thicker THW or XHHW insulation the count is 27.

What is the inside diameter and area of 1-1/4-inch PVC Schedule 80?

The internal diameter is 1.255 in. (31.9 mm) and the total cross-sectional area is 1.237 in². The usable area is 0.495 in² at 40% fill, 0.383 in² for two wires and 0.656 in² for one.

What is the largest wire I can pull three of in 1-1/4-inch PVC Schedule 80?

1 AWG THHN: 3 conductors fit at 40% fill. That is three current-carrying conductors with no ground; add the ground’s area and check again with the calculator if you need one.

Can I really load it with that many conductors?

For space, yes. But 37 current-carrying conductors in one raceway means heavy ampacity derating — 10 to 20 conductors are adjusted to 50% of their table ampacity. Fill tells you what fits; derating tells you what it can carry.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.