3-inch PVC Schedule 40 Conduit Fill

Wire capacity of trade size 3 (metric designator 78) Rigid PVC Conduit, Schedule 40, for THHN, XHHW, THW and RHW conductors from 14 AWG to 1000 kcmil.

3-inch PVC Schedule 40 holds 79 × #8, 57 × #6, 35 × #4 or 25 × #2 THHN conductors at 40% fill. Internal area: 7.268 in²; usable at 40%: 2.907 in².

Internal diameter
3.042 in · 77.3 mm
Total area
7.268 in² · 4689 mm²
40% fill (3+ wires)
2.907 in²
31% / 53% (2 / 1 wire)
2.253 / 3.852 in²
Maximum conductors in 3-inch PVC Schedule 40
Wire sizeTHHNXHHWTHWRHWTHHN in a nipple (60%)THHN area (in²)
14 AWG299209209994490.0097
12 AWG218160160823280.0133
10 AWG137119119662060.0211
8 AWG796666351190.0366
6 AWG57494028860.0507
4 AWG35353022530.0824
3 AWG30302519450.0973
2 AWG25252216370.1158
1 AWG18191511280.1562
1/0 AWG1516139230.1855
2/0 AWG1313118190.2223
3/0 AWG111197160.2679
4/0 AWG9986130.3237
250 kcmil7764110.3970
300 kcmil665490.4608
350 kcmil555380.5242
400 kcmil554370.5863
500 kcmil443360.7073
600 kcmil333150.8676
700 kcmil332140.9887
750 kcmil221141.0496
800 kcmil221141.1085
900 kcmil111131.2311
1000 kcmil111131.3478

Mixed wire sizes? Calculate it

Loading calculator…

3-inch conduit: PVC Schedule 40 vs other types

Trade size is nominal. The real inside diameter, and so the wire count, changes with the wall thickness of each raceway type.

3-inch trade size across conduit types
Conduit typeID (in)Area (in²)40% (in²)#12 THHN#10 THHN#6 THHN
EMT3.3568.8463.53826616769
PVC Schedule 403.0427.2682.90721813757
PVC Schedule 802.8646.4422.57719312251
Rigid Metal Conduit3.0907.4993.00022514259
IMC3.1767.9223.16923815062
Flexible Metal Conduit3.0007.0692.82821213455
Liquidtight Flexible Metal Conduit3.0857.4752.99022514159

Other PVC Schedule 40 sizes

Frequently asked questions

How many #12 wires fit in 3-inch PVC Schedule 40?

218 conductors of 12 AWG THHN/THWN-2 at the 40% fill limit. With thicker THW or XHHW insulation the count is 160.

What is the inside diameter and area of 3-inch PVC Schedule 40?

The internal diameter is 3.042 in. (77.3 mm) and the total cross-sectional area is 7.268 in². The usable area is 2.907 in² at 40% fill, 2.253 in² for two wires and 3.852 in² for one.

What is the largest wire I can pull three of in 3-inch PVC Schedule 40?

700 kcmil THHN: 3 conductors fit at 40% fill. That is three current-carrying conductors with no ground; add the ground’s area and check again with the calculator if you need one.

Can I really load it with that many conductors?

For space, yes. But 218 current-carrying conductors in one raceway means heavy ampacity derating — 10 to 20 conductors are adjusted to 50% of their table ampacity. Fill tells you what fits; derating tells you what it can carry.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.