2-inch IMC Conduit Fill

Wire capacity of trade size 2 (metric designator 53) Intermediate Metal Conduit, for THHN, XHHW, THW and RHW conductors from 14 AWG to 1000 kcmil.

2-inch IMC holds 69 × #10, 39 × #8, 28 × #6 or 17 × #4 THHN conductors at 40% fill. Internal area: 3.630 in²; usable at 40%: 1.452 in².

Internal diameter
2.150 in · 54.6 mm
Total area
3.630 in² · 2342 mm²
40% fill (3+ wires)
1.452 in²
31% / 53% (2 / 1 wire)
1.125 / 1.924 in²
Maximum conductors in 2-inch IMC
Wire sizeTHHNXHHWTHWRHWTHHN in a nipple (60%)THHN area (in²)
14 AWG149104104492240.0097
12 AWG1098080411630.0133
10 AWG695959331030.0211
8 AWG39333317590.0366
6 AWG28242014430.0507
4 AWG17181511260.0824
3 AWG1515139220.0973
2 AWG1212118190.1158
1 AWG9975140.1562
1/0 AWG8864110.1855
2/0 AWG665490.2223
3/0 AWG554380.2679
4/0 AWG444360.3237
250 kcmil333150.3970
300 kcmil332140.4608
350 kcmil231140.5242
400 kcmil111130.5863
500 kcmil111130.7073
600 kcmil111120.8676
700 kcmil111120.9887
750 kcmil111121.0496
800 kcmil111121.1085
900 kcmil111111.2311
1000 kcmil111111.3478

Mixed wire sizes? Calculate it

Loading calculator…

2-inch conduit: IMC vs other types

Trade size is nominal. The real inside diameter, and so the wire count, changes with the wall thickness of each raceway type.

2-inch trade size across conduit types
Conduit typeID (in)Area (in²)40% (in²)#12 THHN#10 THHN#6 THHN
EMT2.0673.3561.3421016326
PVC Schedule 402.0473.2911.316996226
PVC Schedule 801.9132.8741.150865422
Rigid Metal Conduit2.0833.4081.3631026427
IMC2.1503.6301.4521096928
Flexible Metal Conduit2.0403.2691.308986225
Liquidtight Flexible Metal Conduit2.0333.2461.298976125
ENT2.0473.2911.316996226

Other IMC sizes

Frequently asked questions

How many #12 wires fit in 2-inch IMC?

109 conductors of 12 AWG THHN/THWN-2 at the 40% fill limit. With thicker THW or XHHW insulation the count is 80.

What is the inside diameter and area of 2-inch IMC?

The internal diameter is 2.150 in. (54.6 mm) and the total cross-sectional area is 3.630 in². The usable area is 1.452 in² at 40% fill, 1.125 in² for two wires and 1.924 in² for one.

What is the largest wire I can pull three of in 2-inch IMC?

300 kcmil THHN: 3 conductors fit at 40% fill. That is three current-carrying conductors with no ground; add the ground’s area and check again with the calculator if you need one.

Can I really load it with that many conductors?

For space, yes. But 109 current-carrying conductors in one raceway means heavy ampacity derating — 10 to 20 conductors are adjusted to 50% of their table ampacity. Fill tells you what fits; derating tells you what it can carry.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.