2-1/2-inch PVC Schedule 40 Conduit Fill

Wire capacity of trade size 2-1/2 (metric designator 63) Rigid PVC Conduit, Schedule 40, for THHN, XHHW, THW and RHW conductors from 14 AWG to 1000 kcmil.

2-1/2-inch PVC Schedule 40 holds 89 × #10, 51 × #8, 37 × #6 or 22 × #4 THHN conductors at 40% fill. Internal area: 4.695 in²; usable at 40%: 1.878 in².

Internal diameter
2.445 in · 62.1 mm
Total area
4.695 in² · 3029 mm²
40% fill (3+ wires)
1.878 in²
31% / 53% (2 / 1 wire)
1.455 / 2.488 in²
Maximum conductors in 2-1/2-inch PVC Schedule 40
Wire sizeTHHNXHHWTHWRHWTHHN in a nipple (60%)THHN area (in²)
14 AWG193135135642900.0097
12 AWG141103103532120.0133
10 AWG897777431330.0211
8 AWG51434322770.0366
6 AWG37322618550.0507
4 AWG22231914340.0824
3 AWG19191612290.0973
2 AWG16161410240.1158
1 AWG1212107180.1562
1/0 AWG101086150.1855
2/0 AWG8875120.2223
3/0 AWG7764100.2679
4/0 AWG665480.3237
250 kcmil454370.3970
300 kcmil443260.4608
350 kcmil333150.5242
400 kcmil333150.5863
500 kcmil221140.7073
600 kcmil111130.8676
700 kcmil111130.9887
750 kcmil111121.0496
800 kcmil111121.1085
900 kcmil111121.2311
1000 kcmil111121.3478

Mixed wire sizes? Calculate it

Loading calculator…

2-1/2-inch conduit: PVC Schedule 40 vs other types

Trade size is nominal. The real inside diameter, and so the wire count, changes with the wall thickness of each raceway type.

2-1/2-inch trade size across conduit types
Conduit typeID (in)Area (in²)40% (in²)#12 THHN#10 THHN#6 THHN
EMT2.7315.8582.34317611146
PVC Schedule 402.4454.6951.8781418937
PVC Schedule 802.2904.1191.6481247832
Rigid Metal Conduit2.4894.8661.9461469238
IMC2.5575.1352.0541549740
Flexible Metal Conduit2.5004.9091.9641479338
Liquidtight Flexible Metal Conduit2.4934.8811.9521469238

Other PVC Schedule 40 sizes

Frequently asked questions

How many #12 wires fit in 2-1/2-inch PVC Schedule 40?

141 conductors of 12 AWG THHN/THWN-2 at the 40% fill limit. With thicker THW or XHHW insulation the count is 103.

What is the inside diameter and area of 2-1/2-inch PVC Schedule 40?

The internal diameter is 2.445 in. (62.1 mm) and the total cross-sectional area is 4.695 in². The usable area is 1.878 in² at 40% fill, 1.455 in² for two wires and 2.488 in² for one.

What is the largest wire I can pull three of in 2-1/2-inch PVC Schedule 40?

400 kcmil THHN: 3 conductors fit at 40% fill. That is three current-carrying conductors with no ground; add the ground’s area and check again with the calculator if you need one.

Can I really load it with that many conductors?

For space, yes. But 141 current-carrying conductors in one raceway means heavy ampacity derating — 10 to 20 conductors are adjusted to 50% of their table ampacity. Fill tells you what fits; derating tells you what it can carry.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.