4-inch PVC Schedule 40 Conduit Fill

Wire capacity of trade size 4 (metric designator 103) Rigid PVC Conduit, Schedule 40, for THHN, XHHW, THW and RHW conductors from 14 AWG to 1000 kcmil.

4-inch PVC Schedule 40 holds 99 × #6, 61 × #4, 43 × #2 or 27 × 1/0 AWG THHN conductors at 40% fill. Internal area: 12.554 in²; usable at 40%: 5.022 in².

Internal diameter
3.998 in · 101.5 mm
Total area
12.554 in² · 8099 mm²
40% fill (3+ wires)
5.022 in²
31% / 53% (2 / 1 wire)
3.892 / 6.654 in²
Maximum conductors in 4-inch PVC Schedule 40
Wire sizeTHHNXHHWTHWRHWTHHN in a nipple (60%)THHN area (in²)
14 AWG5173613611717760.0097
12 AWG3772772771425660.0133
10 AWG2382062061153570.0211
8 AWG137115115602060.0366
6 AWG998569481480.0507
4 AWG61615137910.0824
3 AWG51524433770.0973
2 AWG43443728650.1158
1 AWG32322619480.1562
1/0 AWG27272216400.1855
2/0 AWG22231914340.2223
3/0 AWG18191612280.2679
4/0 AWG15151310230.3237
250 kcmil1213118190.3970
300 kcmil111197160.4608
350 kcmil9986140.5242
400 kcmil8876130.5863
500 kcmil7765100.7073
600 kcmil555480.8676
700 kcmil554370.9887
750 kcmil444371.0496
800 kcmil444361.1085
900 kcmil443361.2311
1000 kcmil333351.3478

Mixed wire sizes? Calculate it

Loading calculator…

4-inch conduit: PVC Schedule 40 vs other types

Trade size is nominal. The real inside diameter, and so the wire count, changes with the wall thickness of each raceway type.

4-inch trade size across conduit types
Conduit typeID (in)Area (in²)40% (in²)#12 THHN#10 THHN#6 THHN
EMT4.33414.7535.901443279116
PVC Schedule 403.99812.5545.02237723899
PVC Schedule 803.78611.2584.50333821389
Rigid Metal Conduit4.05012.8825.153387244101
IMC4.16613.6315.452410258107
Flexible Metal Conduit4.00012.5665.02637823899
Liquidtight Flexible Metal Conduit4.02012.6925.077381240100

Other PVC Schedule 40 sizes

Frequently asked questions

How many #12 wires fit in 4-inch PVC Schedule 40?

377 conductors of 12 AWG THHN/THWN-2 at the 40% fill limit. With thicker THW or XHHW insulation the count is 277.

What is the inside diameter and area of 4-inch PVC Schedule 40?

The internal diameter is 3.998 in. (101.5 mm) and the total cross-sectional area is 12.554 in². The usable area is 5.022 in² at 40% fill, 3.892 in² for two wires and 6.654 in² for one.

What is the largest wire I can pull three of in 4-inch PVC Schedule 40?

1000 kcmil THHN: 3 conductors fit at 40% fill. That is three current-carrying conductors with no ground; add the ground’s area and check again with the calculator if you need one.

Can I really load it with that many conductors?

For space, yes. But 377 current-carrying conductors in one raceway means heavy ampacity derating — 10 to 20 conductors are adjusted to 50% of their table ampacity. Fill tells you what fits; derating tells you what it can carry.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.