2-1/2-inch IMC Conduit Fill

Wire capacity of trade size 2-1/2 (metric designator 63) Intermediate Metal Conduit, for THHN, XHHW, THW and RHW conductors from 14 AWG to 1000 kcmil.

2-1/2-inch IMC holds 97 × #10, 56 × #8, 40 × #6 or 25 × #4 THHN conductors at 40% fill. Internal area: 5.135 in²; usable at 40%: 2.054 in².

Internal diameter
2.557 in · 64.9 mm
Total area
5.135 in² · 3313 mm²
40% fill (3+ wires)
2.054 in²
31% / 53% (2 / 1 wire)
1.592 / 2.722 in²
Maximum conductors in 2-1/2-inch IMC
Wire sizeTHHNXHHWTHWRHWTHHN in a nipple (60%)THHN area (in²)
14 AWG211147147703170.0097
12 AWG154113113582310.0133
10 AWG978484471460.0211
8 AWG56474724840.0366
6 AWG40352819600.0507
4 AWG25252115370.0824
3 AWG21211813310.0973
2 AWG17181511260.1158
1 AWG1313117190.1562
1/0 AWG111196160.1855
2/0 AWG9986140.2223
3/0 AWG7765110.2679
4/0 AWG665490.3237
250 kcmil554370.3970
300 kcmil444360.4608
350 kcmil443260.5242
400 kcmil333150.5863
500 kcmil332140.7073
600 kcmil111130.8676
700 kcmil111130.9887
750 kcmil111131.0496
800 kcmil111121.1085
900 kcmil111121.2311
1000 kcmil111121.3478

Mixed wire sizes? Calculate it

Loading calculator…

2-1/2-inch conduit: IMC vs other types

Trade size is nominal. The real inside diameter, and so the wire count, changes with the wall thickness of each raceway type.

2-1/2-inch trade size across conduit types
Conduit typeID (in)Area (in²)40% (in²)#12 THHN#10 THHN#6 THHN
EMT2.7315.8582.34317611146
PVC Schedule 402.4454.6951.8781418937
PVC Schedule 802.2904.1191.6481247832
Rigid Metal Conduit2.4894.8661.9461469238
IMC2.5575.1352.0541549740
Flexible Metal Conduit2.5004.9091.9641479338
Liquidtight Flexible Metal Conduit2.4934.8811.9521469238

Other IMC sizes

Frequently asked questions

How many #12 wires fit in 2-1/2-inch IMC?

154 conductors of 12 AWG THHN/THWN-2 at the 40% fill limit. With thicker THW or XHHW insulation the count is 113.

What is the inside diameter and area of 2-1/2-inch IMC?

The internal diameter is 2.557 in. (64.9 mm) and the total cross-sectional area is 5.135 in². The usable area is 2.054 in² at 40% fill, 1.592 in² for two wires and 2.722 in² for one.

What is the largest wire I can pull three of in 2-1/2-inch IMC?

500 kcmil THHN: 3 conductors fit at 40% fill. That is three current-carrying conductors with no ground; add the ground’s area and check again with the calculator if you need one.

Can I really load it with that many conductors?

For space, yes. But 154 current-carrying conductors in one raceway means heavy ampacity derating — 10 to 20 conductors are adjusted to 50% of their table ampacity. Fill tells you what fits; derating tells you what it can carry.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.