5-inch PVC Schedule 40 Conduit Fill

Wire capacity of trade size 5 (metric designator 129) Rigid PVC Conduit, Schedule 40, for THHN, XHHW, THW and RHW conductors from 14 AWG to 1000 kcmil.

5-inch PVC Schedule 40 holds 96 × #4, 68 × #2, 42 × 1/0 AWG or 24 × 4/0 AWG THHN conductors at 40% fill. Internal area: 19.761 in²; usable at 40%: 7.904 in².

Internal diameter
5.016 in · 127.4 mm
Total area
19.761 in² · 12749 mm²
40% fill (3+ wires)
7.904 in²
31% / 53% (2 / 1 wire)
6.126 / 10.473 in²
Maximum conductors in 5-inch PVC Schedule 40
Wire sizeTHHNXHHWTHWRHWTHHN in a nipple (60%)THHN area (in²)
14 AWG81556856826912220.0097
12 AWG5944364362248910.0133
10 AWG3743253251815620.0211
8 AWG216181181943240.0366
6 AWG156134109762340.0507
4 AWG969781591440.0824
3 AWG818269521220.0973
2 AWG686959451020.1158
1 AWG50514129760.1562
1/0 AWG42433526640.1855
2/0 AWG35363022530.2223
3/0 AWG29302519440.2679
4/0 AWG24242116360.3237
250 kcmil20201712300.3970
300 kcmil17171511250.4608
350 kcmil15151310220.5242
400 kcmil1313129200.5863
500 kcmil1111108160.7073
600 kcmil9986130.8676
700 kcmil8876120.9887
750 kcmil7765111.0496
800 kcmil7765101.1085
900 kcmil666591.2311
1000 kcmil665481.3478

Mixed wire sizes? Calculate it

Loading calculator…

5-inch conduit: PVC Schedule 40 vs other types

Trade size is nominal. The real inside diameter, and so the wire count, changes with the wall thickness of each raceway type.

5-inch trade size across conduit types
Conduit typeID (in)Area (in²)40% (in²)#12 THHN#10 THHN#6 THHN
PVC Schedule 405.01619.7617.904594374156
PVC Schedule 804.76817.8557.142537338141
Rigid Metal Conduit5.07320.2128.085608383159

Other PVC Schedule 40 sizes

Frequently asked questions

How many #12 wires fit in 5-inch PVC Schedule 40?

594 conductors of 12 AWG THHN/THWN-2 at the 40% fill limit. With thicker THW or XHHW insulation the count is 436.

What is the inside diameter and area of 5-inch PVC Schedule 40?

The internal diameter is 5.016 in. (127.4 mm) and the total cross-sectional area is 19.761 in². The usable area is 7.904 in² at 40% fill, 6.126 in² for two wires and 10.473 in² for one.

What is the largest wire I can pull three of in 5-inch PVC Schedule 40?

1000 kcmil THHN: 6 conductors fit at 40% fill. That is three current-carrying conductors with no ground; add the ground’s area and check again with the calculator if you need one.

Can I really load it with that many conductors?

For space, yes. But 594 current-carrying conductors in one raceway means heavy ampacity derating — 10 to 20 conductors are adjusted to 50% of their table ampacity. Fill tells you what fits; derating tells you what it can carry.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.