4-inch IMC Conduit Fill

Wire capacity of trade size 4 (metric designator 103) Intermediate Metal Conduit, for THHN, XHHW, THW and RHW conductors from 14 AWG to 1000 kcmil.

4-inch IMC holds 66 × #4, 47 × #2, 29 × 1/0 AWG or 17 × 4/0 AWG THHN conductors at 40% fill. Internal area: 13.631 in²; usable at 40%: 5.452 in².

Internal diameter
4.166 in · 105.8 mm
Total area
13.631 in² · 8794 mm²
40% fill (3+ wires)
5.452 in²
31% / 53% (2 / 1 wire)
4.226 / 7.224 in²
Maximum conductors in 4-inch IMC
Wire sizeTHHNXHHWTHWRHWTHHN in a nipple (60%)THHN area (in²)
14 AWG5623923921868430.0097
12 AWG4103013011546150.0133
10 AWG2582242241243870.0211
8 AWG149124124652230.0366
6 AWG1079275521610.0507
4 AWG66675641990.0824
3 AWG56564836840.0973
2 AWG47474131700.1158
1 AWG35352820520.1562
1/0 AWG29302418440.1855
2/0 AWG24252015360.2223
3/0 AWG20201713300.2679
4/0 AWG17171411250.3237
250 kcmil1314128200.3970
300 kcmil1212107170.4608
350 kcmil101097150.5242
400 kcmil9986140.5863
500 kcmil7875110.7073
600 kcmil665490.8676
700 kcmil555480.9887
750 kcmil554471.0496
800 kcmil554371.1085
900 kcmil444361.2311
1000 kcmil443361.3478

Mixed wire sizes? Calculate it

Loading calculator…

4-inch conduit: IMC vs other types

Trade size is nominal. The real inside diameter, and so the wire count, changes with the wall thickness of each raceway type.

4-inch trade size across conduit types
Conduit typeID (in)Area (in²)40% (in²)#12 THHN#10 THHN#6 THHN
EMT4.33414.7535.901443279116
PVC Schedule 403.99812.5545.02237723899
PVC Schedule 803.78611.2584.50333821389
Rigid Metal Conduit4.05012.8825.153387244101
IMC4.16613.6315.452410258107
Flexible Metal Conduit4.00012.5665.02637823899
Liquidtight Flexible Metal Conduit4.02012.6925.077381240100

Other IMC sizes

Frequently asked questions

How many #12 wires fit in 4-inch IMC?

410 conductors of 12 AWG THHN/THWN-2 at the 40% fill limit. With thicker THW or XHHW insulation the count is 301.

What is the inside diameter and area of 4-inch IMC?

The internal diameter is 4.166 in. (105.8 mm) and the total cross-sectional area is 13.631 in². The usable area is 5.452 in² at 40% fill, 4.226 in² for two wires and 7.224 in² for one.

What is the largest wire I can pull three of in 4-inch IMC?

1000 kcmil THHN: 4 conductors fit at 40% fill. That is three current-carrying conductors with no ground; add the ground’s area and check again with the calculator if you need one.

Can I really load it with that many conductors?

For space, yes. But 410 current-carrying conductors in one raceway means heavy ampacity derating — 10 to 20 conductors are adjusted to 50% of their table ampacity. Fill tells you what fits; derating tells you what it can carry.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.