5-inch PVC Schedule 80 Conduit Fill

Wire capacity of trade size 5 (metric designator 129) Rigid PVC Conduit, Schedule 80, for THHN, XHHW, THW and RHW conductors from 14 AWG to 1000 kcmil.

5-inch PVC Schedule 80 holds 86 × #4, 61 × #2, 38 × 1/0 AWG or 22 × 4/0 AWG THHN conductors at 40% fill. Internal area: 17.855 in²; usable at 40%: 7.142 in².

Internal diameter
4.768 in · 121.1 mm
Total area
17.855 in² · 11519 mm²
40% fill (3+ wires)
7.142 in²
31% / 53% (2 / 1 wire)
5.535 / 9.463 in²
Maximum conductors in 5-inch PVC Schedule 80
Wire sizeTHHNXHHWTHWRHWTHHN in a nipple (60%)THHN area (in²)
14 AWG73651451424311040.0097
12 AWG5373943942028050.0133
10 AWG3382942941635070.0211
8 AWG195163163852920.0366
6 AWG14112198682110.0507
4 AWG868773531300.0824
3 AWG737463471100.0973
2 AWG61625341920.1158
1 AWG45463727680.1562
1/0 AWG38393223570.1855
2/0 AWG32322720480.2223
3/0 AWG26272317400.2679
4/0 AWG22221915330.3237
250 kcmil18181511270.3970
300 kcmil15151310230.4608
350 kcmil1314129200.5242
400 kcmil1212108180.5863
500 kcmil101097150.7073
600 kcmil8876120.8676
700 kcmil7765110.9887
750 kcmil7665101.0496
800 kcmil666491.1085
900 kcmil655481.2311
1000 kcmil555481.3478

Mixed wire sizes? Calculate it

Loading calculator…

5-inch conduit: PVC Schedule 80 vs other types

Trade size is nominal. The real inside diameter, and so the wire count, changes with the wall thickness of each raceway type.

5-inch trade size across conduit types
Conduit typeID (in)Area (in²)40% (in²)#12 THHN#10 THHN#6 THHN
PVC Schedule 405.01619.7617.904594374156
PVC Schedule 804.76817.8557.142537338141
Rigid Metal Conduit5.07320.2128.085608383159

Other PVC Schedule 80 sizes

Frequently asked questions

How many #12 wires fit in 5-inch PVC Schedule 80?

537 conductors of 12 AWG THHN/THWN-2 at the 40% fill limit. With thicker THW or XHHW insulation the count is 394.

What is the inside diameter and area of 5-inch PVC Schedule 80?

The internal diameter is 4.768 in. (121.1 mm) and the total cross-sectional area is 17.855 in². The usable area is 7.142 in² at 40% fill, 5.535 in² for two wires and 9.463 in² for one.

What is the largest wire I can pull three of in 5-inch PVC Schedule 80?

1000 kcmil THHN: 5 conductors fit at 40% fill. That is three current-carrying conductors with no ground; add the ground’s area and check again with the calculator if you need one.

Can I really load it with that many conductors?

For space, yes. But 537 current-carrying conductors in one raceway means heavy ampacity derating — 10 to 20 conductors are adjusted to 50% of their table ampacity. Fill tells you what fits; derating tells you what it can carry.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.