6-inch PVC Schedule 80 Conduit Fill

Wire capacity of trade size 6 (metric designator 155) Rigid PVC Conduit, Schedule 80, for THHN, XHHW, THW and RHW conductors from 14 AWG to 1000 kcmil.

6-inch PVC Schedule 80 holds 88 × #2, 55 × 1/0 AWG, 31 × 4/0 AWG or 14 × 500 kcmil THHN conductors at 40% fill. Internal area: 25.598 in²; usable at 40%: 10.239 in².

Internal diameter
5.709 in · 145.0 mm
Total area
25.598 in² · 16515 mm²
40% fill (3+ wires)
10.239 in²
31% / 53% (2 / 1 wire)
7.935 / 13.567 in²
Maximum conductors in 6-inch PVC Schedule 80
Wire sizeTHHNXHHWTHWRHWTHHN in a nipple (60%)THHN area (in²)
14 AWG105573673634915830.0097
12 AWG77056556529011540.0133
10 AWG4854214212347280.0211
8 AWG2792342341224190.0366
6 AWG202173141983030.0507
4 AWG124125105771860.0824
3 AWG10510690671580.0973
2 AWG888977581320.1158
1 AWG65665438980.1562
1/0 AWG55564633820.1855
2/0 AWG46463929690.2223
3/0 AWG38383325570.2679
4/0 AWG31322721470.3237
250 kcmil25262216380.3970
300 kcmil22221914330.4608
350 kcmil19201713290.5242
400 kcmil17171512260.5863
500 kcmil14141310210.7073
600 kcmil1211108170.8676
700 kcmil101097150.9887
750 kcmil9987141.0496
800 kcmil9987141.1085
900 kcmil8876121.2311
1000 kcmil7775111.3478

Mixed wire sizes? Calculate it

Loading calculator…

6-inch conduit: PVC Schedule 80 vs other types

Trade size is nominal. The real inside diameter, and so the wire count, changes with the wall thickness of each raceway type.

6-inch trade size across conduit types
Conduit typeID (in)Area (in²)40% (in²)#12 THHN#10 THHN#6 THHN
PVC Schedule 406.03128.56711.427859541225
PVC Schedule 805.70925.59810.239770485202
Rigid Metal Conduit6.09329.15811.663877552230

Other PVC Schedule 80 sizes

Frequently asked questions

How many #12 wires fit in 6-inch PVC Schedule 80?

770 conductors of 12 AWG THHN/THWN-2 at the 40% fill limit. With thicker THW or XHHW insulation the count is 565.

What is the inside diameter and area of 6-inch PVC Schedule 80?

The internal diameter is 5.709 in. (145.0 mm) and the total cross-sectional area is 25.598 in². The usable area is 10.239 in² at 40% fill, 7.935 in² for two wires and 13.567 in² for one.

What is the largest wire I can pull three of in 6-inch PVC Schedule 80?

1000 kcmil THHN: 7 conductors fit at 40% fill. That is three current-carrying conductors with no ground; add the ground’s area and check again with the calculator if you need one.

Can I really load it with that many conductors?

For space, yes. But 770 current-carrying conductors in one raceway means heavy ampacity derating — 10 to 20 conductors are adjusted to 50% of their table ampacity. Fill tells you what fits; derating tells you what it can carry.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.