6-inch PVC Schedule 80 Conduit Fill
Wire capacity of trade size 6 (metric designator 155) Rigid PVC Conduit, Schedule 80, for THHN, XHHW, THW and RHW conductors from 14 AWG to 1000 kcmil.
6-inch PVC Schedule 80 holds 88 × #2, 55 × 1/0 AWG, 31 × 4/0 AWG or 14 × 500 kcmil THHN conductors at 40% fill. Internal area: 25.598 in²; usable at 40%: 10.239 in².
| Wire size | THHN | XHHW | THW | RHW | THHN in a nipple (60%) | THHN area (in²) |
|---|---|---|---|---|---|---|
| 14 AWG | 1055 | 736 | 736 | 349 | 1583 | 0.0097 |
| 12 AWG | 770 | 565 | 565 | 290 | 1154 | 0.0133 |
| 10 AWG | 485 | 421 | 421 | 234 | 728 | 0.0211 |
| 8 AWG | 279 | 234 | 234 | 122 | 419 | 0.0366 |
| 6 AWG | 202 | 173 | 141 | 98 | 303 | 0.0507 |
| 4 AWG | 124 | 125 | 105 | 77 | 186 | 0.0824 |
| 3 AWG | 105 | 106 | 90 | 67 | 158 | 0.0973 |
| 2 AWG | 88 | 89 | 77 | 58 | 132 | 0.1158 |
| 1 AWG | 65 | 66 | 54 | 38 | 98 | 0.1562 |
| 1/0 AWG | 55 | 56 | 46 | 33 | 82 | 0.1855 |
| 2/0 AWG | 46 | 46 | 39 | 29 | 69 | 0.2223 |
| 3/0 AWG | 38 | 38 | 33 | 25 | 57 | 0.2679 |
| 4/0 AWG | 31 | 32 | 27 | 21 | 47 | 0.3237 |
| 250 kcmil | 25 | 26 | 22 | 16 | 38 | 0.3970 |
| 300 kcmil | 22 | 22 | 19 | 14 | 33 | 0.4608 |
| 350 kcmil | 19 | 20 | 17 | 13 | 29 | 0.5242 |
| 400 kcmil | 17 | 17 | 15 | 12 | 26 | 0.5863 |
| 500 kcmil | 14 | 14 | 13 | 10 | 21 | 0.7073 |
| 600 kcmil | 12 | 11 | 10 | 8 | 17 | 0.8676 |
| 700 kcmil | 10 | 10 | 9 | 7 | 15 | 0.9887 |
| 750 kcmil | 9 | 9 | 8 | 7 | 14 | 1.0496 |
| 800 kcmil | 9 | 9 | 8 | 7 | 14 | 1.1085 |
| 900 kcmil | 8 | 8 | 7 | 6 | 12 | 1.2311 |
| 1000 kcmil | 7 | 7 | 7 | 5 | 11 | 1.3478 |
Mixed wire sizes? Calculate it
Loading calculator…
6-inch conduit: PVC Schedule 80 vs other types
Trade size is nominal. The real inside diameter, and so the wire count, changes with the wall thickness of each raceway type.
| Conduit type | ID (in) | Area (in²) | 40% (in²) | #12 THHN | #10 THHN | #6 THHN |
|---|---|---|---|---|---|---|
| PVC Schedule 40 | 6.031 | 28.567 | 11.427 | 859 | 541 | 225 |
| PVC Schedule 80 | 5.709 | 25.598 | 10.239 | 770 | 485 | 202 |
| Rigid Metal Conduit | 6.093 | 29.158 | 11.663 | 877 | 552 | 230 |
Other PVC Schedule 80 sizes
Frequently asked questions
How many #12 wires fit in 6-inch PVC Schedule 80?
770 conductors of 12 AWG THHN/THWN-2 at the 40% fill limit. With thicker THW or XHHW insulation the count is 565.
What is the inside diameter and area of 6-inch PVC Schedule 80?
The internal diameter is 5.709 in. (145.0 mm) and the total cross-sectional area is 25.598 in². The usable area is 10.239 in² at 40% fill, 7.935 in² for two wires and 13.567 in² for one.
What is the largest wire I can pull three of in 6-inch PVC Schedule 80?
1000 kcmil THHN: 7 conductors fit at 40% fill. That is three current-carrying conductors with no ground; add the ground’s area and check again with the calculator if you need one.
Can I really load it with that many conductors?
For space, yes. But 770 current-carrying conductors in one raceway means heavy ampacity derating — 10 to 20 conductors are adjusted to 50% of their table ampacity. Fill tells you what fits; derating tells you what it can carry.
NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.